Laserfiche WebLink
1 <br /> P.O. Box 4208 <br /> Sonora CA 95370 <br /> AjjteChPetf'a-- 'r RECEIVED Ca: 623541 A-Haz <br /> Compliance without Compromise AUG 2 5 2016 Phone: 209-532-7320 <br /> Fax: 209-533-2650 <br /> ENVIRONMENTAL mail@alltechpetro.com <br /> HEALTH DEPARTMENT www.alitechpetro.com <br /> LINE LEAK DETECTOR TEST <br /> Facility#: Statewide Petroleum Date: 08/23/16 <br /> Address: 1700 E. Yosemite Ave. <br /> City, State;Manteca, CA <br /> Testing Information <br /> 1 2 4 <br /> Product: 87 91 <br /> Manufacturer vMl I vMl <br /> Leak Detector Serial Number N/A N/A <br /> Leak Detector Model No. LD-2000 LD-2000 <br /> Full Operating Pressure (psi): 34 36 <br /> Test Leak Rate (ml/min)(gph) 3 GPH 3 GPH <br /> Bleed Back Rate (ml): 50 ml 40 ml <br /> Turbine Holding Pressure (psi): 20 psi 20 psi <br /> Metering Pressure (psi): 15-20 psi 15-20 psi <br /> Open/Trip Time (mechanical only): 3s 3s <br /> Pass/ Fail Pass Pass <br /> Comments: <br /> Note: Pass= Leak detector reads leak and meters line. <br /> Fail = Leak detector did not read leak. <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility according to the equipment <br /> manufacturers procedures and limitations and the results as listed are to my knowledge true and correct.'The mechanical leak test <br /> detector test pass/fail is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Alltech Petro Inc <br /> Technician: Isaac Anderson ch Petro Inc. Lic#: 623541 A-Haz <br /> Signature: , ' <br />