Laserfiche WebLink
SWRCB, January 2002 <br />7. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />Page of <br />Test Method Developed By: ❑ UDC Manufacturer ❑ Industry Standard X Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure ❑ Vacuum X Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Caldwell Level Change Indicator <br />Equipment Resolution: .002 <br />EMEMM <br />UDC # 1&2 <br />UDC # 3&4 <br />memo= <br />UDC # 5&6 <br />UDC # 7&8 <br />UDC Manufacturer: <br />Unknown <br />Unknown <br />Unknown <br />Unknown <br />UDC Material: <br />Poly Plastic <br />Poly Plastic <br />Poly Plastic <br />Poly Plastic <br />UDC Depth: <br />26" <br />26" <br />26 %2" <br />27" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />7" <br />8" <br />7 `/z" <br />8" <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />4" <br />4" <br />4" <br />4" <br />Condition of UDC prior to <br />testing: <br />Dry <br />Dry <br />Dry <br />Dry <br />Portion of UDC Tested <br />Water Line 11" <br />Water Line 10" <br />Water Line 12" <br />Water Line 12" <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?` <br />Yes X No ❑ NA <br />Yes X No ❑ NA <br />Yes X No ❑ NA <br />Yes X No ❑ NA <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />safe shutdown?* <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No [INA <br />X Yes ❑ No ❑ NA <br />Was fail-safe verified to be <br />operational?* <br />❑ Yes X No ❑ NA <br />❑ Yes X No ❑ NA <br />❑ Yes X No ❑ NA <br />❑ Yes X No ❑ NA <br />Wait time between applying <br />water and starting test <br />10 Minutes <br />10 Minutes <br />10 Minutes <br />10 Minutes <br />Test Start Time: <br />10:20 <br />10:55 <br />11:00 <br />11:05 <br />Initial Reading (Rj): <br />.001 <br />.001 <br />.001 <br />.001 <br />Test End Time: <br />10:50 <br />11:25 <br />11:30 <br />11:35 <br />Final Reading (RF): <br />.001 <br />.001 <br />.001 <br />.001 <br />Test Duration: <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />Change in Reading (RF-Rl): <br />0 <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />Test Result: <br />X Pass ❑ Fail <br />X Pass ❑ Fail <br />X Pass 0 Fail <br />X Pass ❑ Fail <br />Was sensor removed for testing? <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />