Laserfiche WebLink
INVOICE #bb000292 TEST DATE: 09/04/98 <br /> UNDERGROUND TANK TESTERS <br /> 15806 AVENUE 288 <br /> VISALIA, CA 93292 <br /> 209-747-5220 <br /> TANK STATUS REPORT -- ULLAGE TEST <br /> --------------------------------- <br /> ***** CUSTOMER DATA ***** SITE DATA <br /> WEST STAR ENV. INC. ESCALON MINI MART <br /> 4688 WEST JENNIFIER, SUITE 101 1097 YOSEMITE AVE. <br /> FRESNO,CA. ESCALON, CA. <br /> 93722 95320 <br /> CONTACT: JOHN CONTACT: JACK <br /> PHONE #: 277-9378 PHONE #: 209-837-1546 <br /> COMMENT LINES ***** <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS . 05 GALLONS . <br /> TANK #1 : REG UNLEADED TYPE: STEEL SN: - . 01 <br /> TANK IS TIGHT. <br /> TANK #2 : SUPER UNLEADED TYPE: STEEL SN: - .05 <br /> TANK IS TIGHT. <br /> EX;)"D4 S' ITH <br /> OPERATOR: ---- --- <br /> LIC #911431 SIGNATURE: DATE: b <br /> - ------------- -?/c 6 <br />