r <br />STANDARD <br />MODEL <br />• Self Cleaning <br />• New ®pen Body Design <br />• Stainless Steel Guide Rod <br />• Frictionless Floats <br />i <br />EBW's Newly Designed Auto Limiter 11 <br />The new overfill protection system is an automatic shut-off valve designed to be installed <br />in the 4" riser pipe of underground storage tanks with tight fill adaptor to reduce the flow <br />by 90% at first stage (approximately 92% of tank capacity) and shut down the gravity flow <br />at 95% tank capacity. It is designed to be installed in a spill containment manhole, which <br />makes it unnecessary to break concrete or add a new manhole. The anodized cast <br />aluminum valve body and aluminum drop tubes make the Auto Limiter 11 virtually <br />maintenance free. <br />Automatic Shut -Off Valve for UST's <br />Features <br />Faster deliveries with less restriction <br />Can be set up to 99% of tank capacity <br />Overfill protection at a field -set level <br />Two stage flow shut down provides <br />reduced line shock compared to <br />competitive models: <br />• First stage reduces flow by 90% <br />• Second stage shuts off <br />remaining 10% <br />Anodized cast aluminum valve body <br />Stainless Steel Guide Rod <br />Model for both coaxial installations and <br />dual point systems <br />Accommodates all tank sizes <br />Part no. Size *Lbs. <br />708-450-01 Std. - Up to 10' tank dia. 18.0 <br />708-451-01 Std. - Up to 12' tank dia. 18.5 <br />708-452-01 <br />Std. - Up lo 5' tank dia. <br />'14.3 <br />708-460-01 <br />Coax. - Up to 10' tank dia. <br />18.0 <br />708-461-01 <br />Coax. - Up to 12' tank dia. <br />18.3 <br />708-462-01 <br />Coax. - Up to Stank dia. <br />14.1 <br />708-463-01 <br />Coax. - Poppetted <br />21.1 <br />708-320-01 <br />Check Valve Remote Fill <br />708-321-01 <br />Remote Fill Kit <br />708-453-01 <br />Valve only <br />4.8 <br />Easy field installation without breaking concrete <br />Enables manual stick gaging of tank <br />after a complete shut-off <br />Note: New York City Fire Department <br />Certification # 4959 <br />For N.Y.C. applications, this valve must be <br />installed with a N.Y.C. Fire Department <br />approved spill container. There are additional <br />installation requirements including, but not <br />limited to, product identification and color <br />coding of fills. Installation must comply with <br />applicable codes at time of installation. <br />Sales Desk (800) 475-3291 • Sales Fax (800) 475-4329 • Phone (231) 755-1671 <br />2814 McCracken Avenue, Muskegon, MI 49441 • Fax (231) 755-7201 • http://www.ebw.com <br />® <br />01999 EBW Inc. Form No 1226 6/99 <br />