Laserfiche WebLink
State Water Resources Control Board Page 2 of 3 <br /> LS430A(low level) <br /> Detection time (sec) <1 <1 <1 <br /> Fall time (sec) <1 <1 <1 <br /> Lower detection limit(cm) 8.79 8.48 8.15 <br /> LS-30A(high level) <br /> Detection time (sec) <1 <1 <1 <br /> Fall time (sec) <1 <1 <1 <br /> Lower detection limit(cm) 23.65 23.04 22.78 <br /> LS-7 <br /> Detection time (sec) <1 N/A <1 <br /> Fall time (sec) <1 N/A <1 <br /> Lower detection limit(cm) 1.09 N/A 0.81 <br /> *See glossary. <br /> Specificity Results: <br /> Manufacturer and evaluator claim that sensors will respond to any liquid. <br /> Manufacturer's Specifications: <br /> There is no manufacturer's recommended maintenance schedule. <br /> Comments: <br /> Sensors are reusable. <br /> EBW, Inc. Evaluator: Ken Wilcox Associates <br /> 3760 Marsh Road Tel: (816) 443-2494 <br /> Madison, WI 53718 Dates of Evaluation: 04/20/93, 07/05/94 <br /> Tel: (800) 225-9787 <br /> E-mail: info@franklinfueling.com <br /> URL: www.ebw.com <br /> I Home I Vendors: A - F I Vendors: G -M I Vendors: N -S I Vendors: T-Z I Method Index <br /> Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the <br /> performance of the method or equipment. <br /> Equipment should be installed and operated in accordance with all applicable laws and regulations. <br /> For full details, please refer to our expanded "DISCLAIMER" page. <br /> http://www.waterboards.ca.gov/water issues/programs/ust/leakSrevention/lgl 13/vendors/ebw b.shtml 12/27/2012 <br />