Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for ESCALON MINI MART as of September 12, 2017. <br /> Open violations from December 13, 2016 inspection <br /> Violation#107 -Plot plan/site map not submitted or failed to completely show where monitoring is <br /> performed. <br /> An accurate UST Monitoring Site Plan was not submitted. The site map does not show the location of monitoring <br /> equipment. A site plan must be submitted identifying the locations where monitoring will be performed. Immediately <br /> log into the California Environmental Reporting System (CERS) at http://cers.calepa.ca.gov/and upload a copy of <br /> the UST Monitoring Site Plan. <br /> Violation #201 - Failed to maintain alarm logs and/or records of follow up actions. <br /> Maintenance and monitoring records for the last three years were not found on site. The January 2016 monitoring <br /> system certification test results were not found on site. These records shall be maintained on site for at least three <br /> years. Monitoring records include: (1) date and time of all monitoring or sampling; (2) monitoring equipment <br /> calibration and maintenance records; (3) results of any visual observations; (4) results of sample analysis performed <br /> a lab or in the field; (5) logs of all readings of gauges or other monitoring equipment, ground water elevations, or <br /> other test results; (6) results of inventory readings and reconciliations. Immediately locate and maintain all <br /> maintenance and monitoring records for the last three years on site and submit copies to the EHD. <br /> Open violations from January 11, 2016 inspection <br /> Violation #107 -Plot plan/site map not submitted or failed to completely show where monitoring is <br /> performed. <br /> An accurate UST Monitoring Site Plan was not submitted. A site plan must be submitted identifying the locations <br /> where monitoring will be performed. The submitted map lacks the legend for the utilized symbols identifying <br /> monitoring locations. Immediately log into the California Environmental Reporting System (CERS) at <br /> http://cers.calepa.ca.gov/and upload a copy of the UST Monitoring Site Plan. <br /> Violation #201 -Failed to maintain alarm logs and/or records of follow up actions. <br /> Maintenance and monitoring records for the last three years were not found on site. The onsite alarm logs didn't <br /> document the following alarms: Dec 11, 2015 (91 STP sump).December 31, 2015 (87 STP sump), and December <br /> 31, 2015 (annular sensor). These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1) date and time of all monitoring or sampling; (2) monitoring equipment calibration and maintenance <br /> records; (3) results of any visual observations; (4) results of sample analysis performed a lab or in the field; (5) logs <br /> of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6) results of <br /> inventory readings and reconciliations. Immediately locate and maintain all maintenance and monitoring records for <br /> the last three years on site and submit copies to the EHD. Submit proof of correction to the EHD. <br /> Page 1 of 1 <br />