MARK OF SERVICE I <br />September 8, 1986 <br />Mobil Oil Corporation <br />612 S. Flower St. #933 <br />Los Angeles, California 90017 <br />Attention: Kurt Fischer <br />Re: Mobil Oil NPM 950 <br />16500 I-5 &-Louise, Lathrop, Calif. <br />Dear Mr, Fischer: <br />On August 28, 1986, a Petro Tite System Test was performed` <br />at the above -referenced location. The test was performed by <br />Abel Hernandez, FHEMCO Technician. The NFPA Code 329.02 <br />criteria for a tight. system is a maximum loss of .05 gallons per <br />hour. Because of the almost infinite variables involved, this is <br />not intended to be a mathematical tolerance and is not the permission <br />of actual leakage. <br />During the stand -pipe test procedure., the .internal liquid <br />hydrostatic pressure applied to the underground tank system -is - <br />generally two to three times greater`thari-"normal liquid storage <br />pressures. This increase in hydrostatic pressure will amplify <br />the indicated rate of leak accordingly. <br />SYSTEM TEST <br />Tank No. 1 - North <br />Size - 10,000 Gallons <br />Product - Unleaded <br />The test showed a plus .028 gallons per hour. <br />Based on the above criteria, we find the tank tested <br />mathematically tight. <br />Tank No. 2 ;.Middle <br />Size - 6,000 Gallons <br />Product - Super Unleaded_ <br />The test showed a minus .006 gallons per hour. <br />Based on the above criteria, we find the tank tested <br />mathematically tight. <br />3040 W Street - (805) 323-8136 <br />BAKERSFIELD, CA 93301 <br />F & H EQUIPMENT MAINTENANCE COMPANY <br />- HOME OFFICE - <br />1100 North V Street - (209) 688-2977 <br />Post Office Box 88 - TULARE, CA 93275-0088 <br />17068 Road 26 - (209) 675-1000 <br />MADERA, CA 93638 <br />