Laserfiche WebLink
Triangle Environmental, Inc. <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Corp. Facility # 30225 <br /> Tank #: 1 Test Date: 9/23/02 <br /> Product: Unleaded Regular Work#: 12901074 <br /> MENEEMEMEM <br /> Test Method: Test Method: R.J.FTA k <br /> Capacity: 11849 Manufacturer: FE Petro <br /> Diameter(in): L/D Model: i <br /> f <br /> Product Level(in): LID Serial#: can't read ! <br /> Liquid Volume(Gals): Line Drain Back(ml): 120 f <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 28 l <br /> Coef.of Expansion: Metering Pressure(psi): 11 { <br /> Water On Tank(in): L/D Test Rate(gph): 2.7 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: FE Petro <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure(psi): 51 <br /> Line Start Time: 11:15:00 AM <br /> Test Method: ULLAGE Line End Time: 11:30:00 AM <br /> UllageVolume(gals.): Line Start Level: 350 <br /> Ullage Test Time: Line End Level: 345 <br /> Ullage Vacuum(psi): Line Test Rate(gph): -0.005 <br /> Ullage Result: N/A Line Test Result: PASS <br /> FEPetro S`I'PMLD <br />