Recommended Practices for the Testing and Verification of Spill,Overfill,leak Detection and Secondary Containment Equipment at UST Facilities <br /> Verify that the console has no active or i <br /> recurring history of leak detection-related <br /> warnings or alarms. In the event of any <br /> such warnings or alarms,notify the appro- <br /> priate person before continuing the test. <br /> Where possible print out the system setup <br /> and any alarm histories from the console. fi <br /> Save the printout for facility records or <br /> make an electronic copy. 4 <br /> I <br /> .2.1.5 Test Equipment. Test equip- <br /> ment shall include: <br /> • tools for the removal of the ATG probe <br /> and sensors; <br /> • tape measure or gauge stick; <br /> • water-finding paste. <br /> .2.1.6 Test Procedure. <br /> 1. Measure the product and water level <br /> in the tank and compare to the console <br /> readings to confirm ATG accuracy. If <br /> the readings do not agree, contact the FIGURE 8-2. When removing and replacing the ATG o <br /> appropriate rson. s <br /> Pe probe, be careful to avoid damaging any of the compo- <br /> . Remove the ATG probe cap and vents. <br /> disconnect the cable from the ATG. <br /> . Clear the alarm conditions. <br /> . Remove the ATG probe from the tank. 0. For the water float, slowly move the <br /> Use care to ensure that the floats on float up the probe until the water <br /> the stem do not catch on the bottom alarm is triggered. <br /> of the riser during removal. <br /> . Inspect the probe. The floats must 11. Measure the distance from the bottom <br /> move freely on the stem without of the probe to the water float when <br /> the float first triggers the water alarm. <br /> binding. If any parts are damaged <br /> or missing, contact the appropriate 12. Compare the measurements for prod- <br /> person. uct float and the water float in Steps 8 <br /> . Reconnect the probe cable. and 11 to the values programmed into y <br /> the console. <br /> . Set the fuel float in the middle of the <br /> probe and verify that it is showing the 8.2.1.7 Pass/Fail Criteria. If the mea- <br /> correct inch reading on the console. surements for the product and water floats <br /> match the values programmed in the con- <br /> 7. Slowly move the fuel float up the sole and the console acknowledges the 3 <br /> probe until the high product alarm is high product and water level alarms, the <br /> triggered on the console.If the system ATG probe passes the test. <br /> does not alarm at the pre-set level, <br /> contact the appropriate person. If the measurements for the product and <br /> S. Measure the distance from the bottom water floats do not match the values pro- <br /> of the probe to the fuel float when the grammed in the console or the console <br /> float first triggers the high product does not acknowledge the high product <br /> alarm or water level alarms, the ATG probe fails <br /> the test. <br /> peLorg 0 <br />