SWRCB, January 2002 Page <br />8. FILL RISER CONTAINMENT SUMP TESTING A L.1, 2 1 <br />Facility is Not Equipped With Fill Riser Containment Sums <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ , (, <br />Test Method Developed By: ❑ Sump Manufacturer ❑ Industry Standard X Professional Engineer . <br />❑ Other (Spec) <br />Test Method Used: <br />Pressure Vacuum X Hydrostatic <br />Other (Spec) <br />Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br />Fill Sump # 1 Fill Sump # Fill Sump # Fill Sump # <br />Sump Diameter: <br />42" <br />Sump Depth: <br />45 ''/2" <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />23 'h" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />26" <br />Condition of sump prior to <br />testing: <br />Dry <br />Portion of Sump Tested <br />Water Line 28 ''/s" <br />Sump Material: <br />Fiberglass <br />Wait time between applying <br />water and starting test: <br />5 Minutes <br />Test Start Time: <br />11:40 <br />Initial Reading (Rj): <br />.001 <br />Test End Time: <br />12:10 <br />Final Reading (RF): <br />.001 <br />Test Duration: <br />30 Minutes <br />Change in Reading (RF -R,): <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />Test Result: <br />Pass <br />Is there a sensor in the sump? <br />Yes <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />Yes <br />Was sensor removed for testing? <br />Yes <br />Was sensor properly replaced and Yes <br />verified functional after testin ? <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />