Laserfiche WebLink
. cisioN <br /> INDUSTRIES 1041 S. PERSHING AVE., STOCKTON, CALIFORNIA 95206 <br /> 209/462-9911 NO. CALIF. 800/332-5900 FAX 209/462-2024 <br /> CALIFORNIA STATE LIC. 467293 <br /> INC <br /> January 03, 1990 <br /> SAN JOAQUIN COUN'T'Y E.H.D. <br /> TANK REMOVAL PROCEDURE <br /> Site Name: Mel Bokides Petroleum, Inc. <br /> Cardlock Number 2 <br /> Site Address: 983 Moffat Blvd. <br /> Manteca, CA. <br /> TANK SIZES <br /> One (1) 10,000 gallon diesel tank. <br /> One (1) 4,000 gallon unleaded gasoline tank. <br /> One (1) 3,000 gallon supreme gasoline tank. <br /> One (1) 4,000 gallon regular gasoline tank. <br /> LIQUID PZ40VAL <br /> All liquids in tanks will be removed by Mel Bokides Petroleum, <br /> 2191 Navy Drive, Stockton, CA. 95206. <br /> DEGAS <br /> Each tank will have (Minimum 15#/1000 gallon) dry ice inserted <br /> before removal proceeds. <br /> i.e. 10,000 gallon - 150# dry ice <br /> each 4,000 gallon - 60# dry ice <br /> 3,000 gallon - 45# dry ice <br /> TANK DISPOSAL <br /> The tanks and piping will be manifested and hauled as hazardous waste. <br /> The piping and tanks will be hauled and disposed of by Erickson <br /> Inc., 255 Parr Blvd., Richmond, CA. 94801. EPA I.D. number <br /> CAD009466392. <br /> SAMPLES <br /> Two (2) soil samples will be taken under each tank. One at each <br /> end of the tank at 2' to 4' below the tank bottom. Also one (1) <br /> sample will be taken every 20 lineal feet of piping at 2' to 4' <br /> below piping. <br />