Laserfiche WebLink
UNDER DISPER CONTAINMENT *C) TESTING <br />Test Method By: O Manufacturer • Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: O Pressure o Vacuum • Hydrostatic o Other (see below) <br />Measuring Equipment Used: INCON TS -STS (Electronic Sump Test System) <br />UDC manufacturer <br />UDC material <br />UDC depth (inches) <br />Height from UDC bottom to highest <br />piping penetration <br />Height from UDC bottom to lowest <br />electrical penetration <br />Condition of UDC prior to testing <br />Portion of UDC tested <br />Type of shut -down present <br />Was sensor removed for testing? <br />Was sensor properly replaced after testing <br />ulsp ;; vz <br />ulsp ;; s14 <br />ulsp ;li bib <br />u1s ;; //a <br />Total Containment <br />Total Containment <br />Total Containment <br />Total Containment <br />Poly <br />Poly <br />Poly <br />Poly <br />38 <br />6 <br />38 <br />10 <br />38 <br />14 <br />38 <br />13 <br />10 <br />6 <br />10 <br />10 <br />Dry <br />Sensor <br />Yes <br />Yes <br />Depth of water level from UDC bottom (in.) <br />22 <br />Wait time for water level to stabilize (hr:min) <br />0:10 <br />Test start time <br />8:44 AM <br />Initial Probe Reading <br />3.2733 <br />Test end time <br />8:59 AM <br />Final Probe Reading <br />3.2722 <br />Test duration (hr:min) <br />0:15 <br />Change in water level (± 0.0000 inches) <br />-0.0011 <br />Pass/Fail threshold (±0.0020 inches /; Hr.) <br />0.0020 <br />TEST RESULT <br />PASS <br />2004 Walton Engineering, Inc. <br />