Laserfiche WebLink
Jul 14 03 05:29p Ch6 ity Miles <br />AlItech <br />17759 Buttercup Circle, Sonora, CA 95370 <br />Phone: 209-532-7320; Fax: 209-533-2650 <br />California Tank Tester: 90-1068 <br />California Contractor 623541 A-Haz <br />alltech(ii;nilodexom <br />(20,W 533-2650 <br />4P <br />Precision Test Data Sheet for Line Leak Detectors <br />Vaporless LDT-890 <br />Facility: Olympian Ca-rdlock <br />Address: 983 Moffat Blvd <br />City: Manteca CA <br />Facility contact: Nick Bokides <br />L.I.A.: San Joaquin <br />Phone: 234-1256 <br />L.I.A. Phone: <br />p.4 <br />Date: Jul. 11, 03 <br />Product 4 SUL <br />DSL <br />Turbine manufacturer R.J. <br />_UL <br />R.J. <br />R.J. <br />Leak Detector mfr RJ XL <br />RJ XL <br />Vap2K <br />L.D. search pressure 11 <br />11 <br />10 <br />Step -through time- seconds 3 <br />3 <br />2 <br />Turbine operating pressure 31 <br />31 <br />35 <br />Line holding pressure- psi 26 <br />31 <br />35 <br />Bleed back test- ml 100 <br />120 <br />150 <br />10 p.si flow quantity- ml 95 <br />95 <br />95 <br />Leak detector stays tripped? Yes <br />Yes <br />Yes <br />Conclusion: * Pass/ Fail PaSS <br />Pass <br />Pass <br />- Mass = Leak Uetector stays in slow -flow during GPH Test; <br />Fail = Leak Detector steps through to allow full pump pressure during GPH <br />Test. <br />Remarks: <br />v <br />Test tech: ?RJ6e 42�� Mike Dotten, License 90—I068Rev.6/7/2002 <br />