9 0 <br />UNDER DISPENSER CONTAINMENT (UDC) TESTING <br />...Manufacturer:.::x, below):: <br />0:0ther (see <br />TestMe.thod, Uses: p Pressure 0 Vacuum I 1 01, Hydrostatic 1 . xx: 0 1 Dt her (see I below): <br />.... <br />Measuring xqujumeO:l sod LeI—Ch- <br />anowI Indicator (Caldwell Systen:2001 f WaltonEngineering) <br />Descrilottow.., Disc #>8 ZAt <br />UDC Manufacturer <br />Total Containment <br />UDC Material <br />Poly <br />UDC Depth (inches) <br />38" <br />Height from UDC bottom to highest <br />piping penetration <br />Height from UDC bottom to lowest <br />12" <br />electrical penetration <br />Condition of UDC prior to testing <br />Wet <br />Portion of UDC tested <br />Entire <br />Type of shut -down present <br />Sensor <br />Was sensor removed for testing? <br />Yes <br />Was sensor properly replaced after testing? x: <br />Yes <br />Waft time for water level to stabilize <br />0:26 <br />Depth of water level from UDC bottom (in.) <br />16, <br />Test start time <br />11:54 AM <br />Test end time <br />12:24 PM <br />Test duration <br />0:30 <br />Change in water level 0.000 inches) <br />0.00() <br />Pass/Fail threshold (0.005 inches Hr.) <br />0.005 <br />TEST RESULT <br />PASS <br />Comments: <br />UDC for dispenser #8 Sat: This is a satellite to master dispenser 7/8. <br />© 2002 Walton Engineering, Inc. <br />