Laserfiche WebLink
REGEIVEEI�"i <br /> UNDER DISPENSERCONTAINMENT ( _C) TEST114615 <br /> W p®amu" rt -rAfic%r° <br /> Test Method By: o Manufacturer • industry standard o Professional Engr o Other(see below) <br /> Testi Method Uses: 0 'Pressure 0 vacuum • Hydrostatic o Other(see below) <br /> Measuring Equipment Used: "INCON TS-STS (Electronic Sump Test System) <br /> Description Disp#8 Sat <br /> UDC manufacturer Total Containment <br /> UDC material Poly <br /> UDC depth (inches) 38 <br /> Height from UDC bottom to highest 8 <br /> piping penetration <br /> Height from UDC bottom to lowest 12 <br /> electrical penetration <br /> Condition of UDC prior to testing Dry <br /> Portion of UDC tested Entire <br /> Type of shut-down present Sensor <br /> Was sensor removed for testing? Yes <br /> Was sensor properly replaced after testing? Yes <br /> Depth of water level from UDC bottom (in.) 14 <br /> Wait time for water level to stabilize (hr:min) :10 <br /> Test start time 1:44 PM <br /> Initial Probe Reading 3.3122 <br /> Test end time 1:59 PM <br /> Final Probe Reading 3.3121 <br /> Test duration (hr:min) 0:15 <br /> Change in water level (±0.0000 inches) -0.0001 <br /> Pass/Fail threshold (±0.002 inches/;Hr.) 0.0020 <br /> TEST RESULT PASS <br /> Comments: <br /> 0 2015 Walton Engineering,Inc. <br />