low lqw <br /> UNDER DISPENSER CONTAINMENT (UDC) TESTING <br /> Test Method By: o Manufacturer • Industry Standard o Professional Engr o Other(see below) <br /> Test Method Uses: o Pressure o Vacuum • Hydrostatic o Other(see below) <br /> Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br /> Description Dis #1/2 Disp#3/4 Disp#5/6 Disp#7/8 <br /> UDC manufacturer Total Containment Total Containment Total Containment Total Containment <br /> UDC material Poly Poly Poly Poly <br /> UDC depth (inches) 38 38 38 38 <br /> Height from UDC bottom to highest 6 10 14 13 <br /> piping penetration <br /> Height from UDC bottom to lowest 10 6 10 10 <br /> electrical penetration <br /> Condition of UDC prior to testing Dry Dry Dry Dry <br /> Portion of UDC tested Entire Entire Entire Entire <br /> Type of shut-down present Sensor Sensor Sensor Sensor <br /> Was sensor removed for testing? Yes Yes Yes Yes <br /> Was sensor properly replaced after testing? Yes Yes Yes Yes <br /> Depth of water level from UDC bottom (in.) 8 12 <br /> Wait time for water level to stabilize (hrmin) :10 :10 <br /> Test start time 2:38 PM 2:38 PM NOVnitial Probe Reading 5.1924 4.6257 !wI <br /> Test end time 2:53 PM 2:53 PM <br /> Final Probe Reading 5.1922 4.6254 ENVIRONMEtNITIT <br /> Test duration (hr:min) 0:15 0:15 <br /> Change in water level (±0.0000 inches) -0.0002 -0.0003 <br /> Pass/Fail threshold (±0.002 inches/;Hr.) 0.0020 0.0020 <br /> TEST RESULT PASS PASS <br /> Comments: <br /> 0 2015 Walton Engineering,Inc. <br />