Laserfiche WebLink
SECONDARY LINE TESTING <br /> 11 APR 2 4 2015 <br /> ENVIRONMENTAL <br /> Test Method By: O Manufacturer • Industry Standard o Professional 0TdV o'8Fh'9rTsee%ow) <br /> Test Method Uses: • Pressure o vacuum o Hydrostatic o Other(see below) <br /> Measuring Equipment Used: Pressure Gauge (range 0 to 15 psig) <br /> Description Line#1 Line#2 Line#3 <br /> Tank product Gasoline-87 Gasoline-91 Diesel <br /> Pipe manufacturer Ameron Ameron Ameron <br /> Pipe material FRP FRP FRP <br /> Primary pipe diameter (inches) 2 2 3 <br /> Secondary pipe diameter (inches) 3 3 4 <br /> Method of secondary pipe isolation Termination Boot Termination Boot Termination Boot <br /> Location of secondary pipe isolation Sump Sump Sump <br /> Estimated length of piping run (feet) 110 80 130 <br /> (include length of branch runs) <br /> Wait time for pressure to stabilize (hr:min) :05 <br /> Test start time 9:34 AM <br /> Initial pressure (psig) 5.0 <br /> Test end time 10:34 AM <br /> Final pressure(psig) 5.0 <br /> Test duration (hrmin) 1:00 <br /> Change in pressure (psig) 0.0 <br /> Pass/Fail threshold (psig) 0.5 <br /> TEST RESULT PASS <br /> Comments: <br /> #8 Secondary Sat Line tested at 9:37 am to 10:37 am at 5 psi,with passing results. <br /> 0 2015 Walton Engineering,Inc. <br />