Laserfiche WebLink
AES/System II Precision leak Test Graph (OverFill) <br />Invoice No.i 18776 Dates 02/24/94 Time It 18:08:19 <br />Technicians PDB Tanks 2 Tank Diameter(in)z 95 <br />Volume(gal)l 8000 Grade Level(in)s 129 Product Level(in)s 155 <br />Water Level On Tank(in)s 0 <br />Specific Gravity: .74 Coefficient Of Expansion: 0.0006835 <br />Calibration Value(ml): 500 Channel: 2 <br />Level Segment Froms 75 To 300 Temp Segment From: 75 To 300 <br />L <br />E <br />V <br />E <br />L <br />----- - ---- --- <br />—era" <br />- - ----- ----- <br />Change In Calibration Zone = 66 <br />Starting Temperature (F)s 57.178 <br />Surface Area(sq. in): 46.8 <br />Calibration Unit(gal/unit) = 0.00200 <br />Head Pressure(psi (Btm))i 4.14 <br />Temp. Change(F/h) : 0.010 <br />Level volume (gph) 1 0.02 <br />Temp. volume (gph): 0.05 Product Line (gph)s 0.00 <br />Net change(gph) 1 -0.03 <br />R w % s -A I > F=N A:=k S; a <br />Copyright (c) 1991, AES, Bakersfield, California <br />Notes <br />MOSSDALE TEXACO <br />444 MOSSDALE RD. <br />LATHROP, CA. <br />WATER TABLE IS AT 141 PER SJ COUNTY HEALTH DEPT. <br />