Laserfiche WebLink
LINE LEAK DETECTOR (LLD) TEST REPCA-tU1=1Vt <br />TEST DATE: July 1, 2015 _ _ 9_ <br />-- <br />A1. FACILITY A2. OWNER <br />Name Ouik Stop Market # 76 Name Quik Stop Markets, Inc.ENVIRONMENT <br />Address 1030 S. Olive Avenue, Stockton, CA 95215 Address 4567 Enterprise Street, Fremogt; f;Ar 1%oTgAj=nl-i <br />Phone # 510-657-8500 Phone # 510-657-8500 <br />Contact Roger Batra Contact Debbie Markovich <br />A3. C U P A <br />A4. TESTING CONTRACTOR <br />Name <br />San Joaquin County Environmental Health <br />1 <br />Name <br />Walton Engineering, Inc. <br />Address <br />1868 E. Hazelton Avenue, Stockton, CA 95202 <br />Gasoline -87 <br />Address <br />P.O. Box 1025, W. Sacramento, CA 95691 <br />Notified <br />June 18, 2015 <br />MLLD <br />Lic # <br />617238 A, B, Haz <br />Inspector <br />Cindy Vo <br />FE Petro STP -MLD <br />Contact <br />Veronica Freitas <br />Phone # <br />209-468-8257 <br />Illegible <br />Phone # <br />916-373-1166 <br />I1. LINE LEAK DETECTOR TEST RESULTS I <br />Toot Gni dnmant 1 1-4- V.—I... \/EAI I r1T_GDA <br />J. COMMENTS: <br />Signature: <br />AeNA% 7Fs WALTON <br />ENGINEERING, INC. <br />Technician: Thomas Steiger A31060 / 8156310 Date: July 1, 2015 <br />Tank number <br />1 <br />2 <br />Product contained <br />Gasoline -87 <br />Gasoline -91 <br />Leak Detector Type <br />MLLD <br />MLLD <br />Leak detector make/model <br />FE Petro STP -MLD <br />FE Petro STP -MLD <br />Serial number <br />Illegible <br />Illegible <br />Functional Element Holding (psi) <br />24 <br />20 <br />Resiliency (ml) <br />95 <br />100 <br />Test leak rate (gph) <br />3.00 <br />3.00 <br />Pump pressure (psi) <br />24 <br />28 <br />Metering pressure (psi) <br />10 <br />9 <br />Pressure Restriction Reduction (psi) <br />14 <br />19 <br />Length of Restriction Test (seconds) <br />30 <br />30 <br />Full Flow Opening time (seconds) <br />9 <br />3 <br />TEST RESULT <br />PASS <br />PASS <br />Tank number <br />Product contained <br />Leak Detector Type <br />Leak detector make/model <br />Serial number <br />Functional Element Holding (psi) <br />Resiliency (ml) <br />Test leak rate (gph) <br />Pump pressure (psi) <br />Metering pressure (psi) <br />Pressure Restriction Reduction (psi) <br />Length of Restriction Test (seconds) <br />Full Flow Opening time (seconds) <br />TEST RESULT <br />J. COMMENTS: <br />Signature: <br />AeNA% 7Fs WALTON <br />ENGINEERING, INC. <br />Technician: Thomas Steiger A31060 / 8156310 Date: July 1, 2015 <br />