Laserfiche WebLink
INVOICE #WCO01058 <br />USTest 2000 / P <br />CHAMPION PRECISION TANK TESTING <br />P.O. BOX 13059 <br />SACRAMENTO CA 95813-3059 <br />TANK STATUS EVALUATION REPORT <br />----------------------------- <br />***** CUSTOMER DATA ***** <br />OIL EQUIPMENT SERVICE <br />P 0 BOX 950 <br />SAN ANDREAS,CA. <br />95249 <br />1410RIN <br />lV00104m: 0 .I <br />. <br />TEST DATE: 04/29/99 <br />***** SITE DATA ***** <br />WATERLOO FOOD AND FUEL <br />3025 EAST WATERLOO ROAD <br />WATERLOO AND SUTRO AVE. <br />STOCKTON,CA. <br />95205 <br />1 <br />***** COMMENT LINES ***** <br />NEW SECONDARY CONTAINMENT SYSTEM <br />INCON TS -LLD AUTO SHUT DOWN <br />BLENDER DISPENSERS <br />CURRENT EPA STANDARDS DICTATE <br />THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE THRESHOLD RATE <br />OVER THE PERIOD OF ONE HOUR IS .05 GALLONS. <br />ABOVE STATEMENT N/A FOR THE ULLAGE TEST.MAXIMUM SN:IS +/- 2.0 <br />TANK #1: REG UNLEADED TYPE:FIBERGLASS RATE: .035925 G.P.H. GAIN <br />TANK IS TIGHT. <br />TANK #2: SUPER UNLEADED TYPE:FIBERGLASS RATE: .020282 G.P.H. GAIN <br />TANK IS TIGHT. <br />TANK #3: DIESEL FUEL 2 TYPE:FTBERGLASS RATE: .008084 G.P.H. GAIN <br />TANK IS TIGHT. <br />OPERATOR: SIGNATURE: �-- - �- -------- DATE: <br />