Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑Tank Manufacturer ❑Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑Hydrostatic <br /> ❑Other(Sped) <br /> Test Equipment Used:VACUUM Equipment Resolution:"Hg <br /> Tank#87 Tank#91/DSL Tank# Tank# <br /> Is Tank Exempt From Testing?' ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Tank Capacity: 15K 15K <br /> Tank Material: STEEL STEEL <br /> Tank Manufacturer: UNKNOWN UNKNOWN <br /> Product Stored: FUEL FUEL <br /> Wait time between applying <br /> pressure/vacuum/water and <br /> starting test: <br /> Test Start Time: 1030 1135 <br /> Initial Reading(R,): <br /> 7" 7" <br /> Test End Time: 1130 1235 <br /> Final Reading(RF): 7" T' <br /> Test Duration: IHR IHR <br /> Change in Reading(RF-R,): 0 0 <br /> Pass/Fail Threshold or Criteria: 2 2 <br /> Test Result: Pass ❑Fail C"Pass ❑Fail ❑ Pass ❑Fail D Pass ❑Fail <br /> Was sensor removed for testing? ®'Yes ❑No ❑NA 1'Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and Aes ❑No ❑NA iJ Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> verified functional after testing? 1. <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)} <br />