Laserfiche WebLink
Page 1 of 1 <br /> SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Fill Riser Containment Sumps <br /> Fill Riser Containment Sumps are Present, but were Not Tested <br /> Test Method Developed By: r Spill Bucket Manufacturerto Industry Standard r Professional Engineer <br /> r Other (Specify): <br /> Test Method Used By: r Pressure f vacuum t« Hydrostatic <br /> r Other (Specify): <br /> Test Equipment Used: LAKE TEST Equipment Resolution: 0.025 in. <br /> $Ptll > ox € Spill Box,#, <br /> Tank T1% 0 Tank T2 RSG UNLEA© Spill Box # SpilE Scxk <br /> Fill iirct . ' Till - Direct <br /> Bucket Diameter: 12.00 12.00 <br /> Bucket Depth: 14.00 14.00 <br /> Wait time between applying <br /> pressure/vacuum/water and 5 min 5 min min min <br /> starting test <br /> Test Start Time: 10:37:00 10:37:00 <br /> Initial Reading(R,): 14.00 in. 14.00 in. <br /> Test End Time: 11:37:00 11:37:00 <br /> Final Reading fw: 14.00 in. 14.00 in. <br /> Test Duration: 1 hr 1 hr <br /> Change in Reading �,>: 0.00 in. 0.00 in. <br /> Pass/Fail Threshold or Criteria: +/- 0.00 +/- 0.00 <br /> Test Result: Pass Pass <br /> Comments? (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> WO: 2308164 <br />