4. SPILL/OVERFILL CONTAINMENT BORE. <br /> °a <br /> Facility is Not Equipped With Spill/Overfil tainment Boxes <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested <br /> -Test Method Developed By: Spill Bucket Manufacturer ® Industry Standard Professional Engineer <br /> Other(Specify) <br /> Test Method Used: Pressure Vacuum ®Hydrostatic <br /> Other(Spec) <br /> Test Equipment Used: VISUAL/MEASURE Equipment Resolution: N/A <br /> Spill Boz#1 Spill Box Spill Box# Spill Boz# <br /> DIESEL FILL <br /> RBucketDiameter: 12" <br /> Bucket Depth: 14" <br /> Wait time between applying <br /> pressure/vacuum/water and 5 MINUTES <br /> starting test: <br /> Test Start Time: 9:00 <br /> Initial Reading(R,): 6" <br /> Test End Time: 10:00 <br /> Final Reading(RF): 6" <br /> Test Duration: 1 HOUR <br /> Change in Reading(RF-R,): 0 <br /> Pass/Fail Threshold or 0 <br /> Criteria: <br /> Test Result: ® Pass Fail ❑ Pass Fail Pass Fail Pass Fail <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />