Laserfiche WebLink
.s <br /> Monthly/Annual Testing <br /> Attachment 4 <br /> Data Sheet Summarizing the Product Temperature Conditions Used in the Evaluation <br /> Pipeline Leak Detection System <br /> Options 1 and 5 <br /> Test No. Date Nominal Time Time Duration of Time of T(TB) T(1) T(2) T(3) T(G) T(TB)-T(G) Temperature <br /> (Based on Test Product Circulation Circulation Circulation Temperature Test <br /> Temperature Began Temperature Started Ended Measurements Matrix <br /> Condition and Before Category <br /> Type of Circulation <br /> Pipeline) Was Started <br /> (D-M-Y) (deg F) (local military) (deg F) (h-min) (local military) (deg F) (deg F) (deg F) (deg F) (deg F) (deg F) (Table 5.1) <br /> Flex-2 3-Mar-98 24.50 1705 1805 0100 1705 24.50 47.90 47.80 48.40 48.21 -23.71 <-25 <br /> Flex-3 23-Feb-98 46.98 0628 0728 0100 0628 46.98 47.80 47.70 47.60 47.64 -0.66 -5 to+5 <br /> Flex-4 23-Feb-98 48.49 1316 1416 0100 1316 48.49 47.91 47.68 47.61 47.66 0.83 -5 to+5 <br /> Flex-5 119-Feb-981 71.00 1727 1827 0100 1727 71.00 46.20 46.10 46.00 46.04 24.96 1 >+25 <br /> Flex-6 120-Feb-981 71.70 1 1107 1 1212 1 0105 1 1107 1 71.70 47.00 46.80 46.50 46.62 25.08 1 >+25 <br />