Laserfiche WebLink
Insl <br />Equipment Preparation <br />OCT 2 4 2014 <br />To prepare your equipment for sensor installation: <br />1. Turn Off power to the console. r � <br />2. Make sure no liquid is present in the annular space. Do not install the sensor if any liquid is presenYiffthe'�I <br />annular space.Failure to comply will lead to an alarm. <br />i <br />3. An eyelet has been' provided at the end of the sensor for attaching the pull -cord. <br />4. To ensure the sensor will reach the bottom of the annular space, the splice between the leder cable and the <br />sensor must be 1 foot from ,the bottom of the riser pipe (Figure 2). <br />a. First measure the sensor riser pipe from the bottom of the pipe to the top. <br />b. Subtract 1 foot from the riser pipe measurement, <br />c. Measure the distance up the leader cable from its (connection to the sensor; mark the loader cable with' a <br />piece of tape. <br />i <br />Installation of Float Sr vitch <br />To ensure proper, operation of the float switch, it is important that you install a sensor with the correct cable length. <br />This ensures the float switch will rest as close as possible to the bottom of the tank annulus (Figure 2) <br />i <br />Weatherproof 'unction box with <br />1/2 -inch N.P.T. threads (16 Cubic <br />14" min. dia. manhole inch volume minimum) <br />4 <br />