UNDER DISPENSER CONTAINMENT DC) TESTING <br /> Test Method By: O Manufacturer • Industry Standard o Professional Engr o Other(see below) <br /> Test Method Uses: O Pressure O Vacuum • Hydrostatic o Other(see below) <br /> Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br /> Description Disp#1/2 Disp#3/4 Disp#516 <br /> UDC manufacturer Bravo Bravo Bravo <br /> UDC material FRP FRP FRP <br /> UDC depth (inches) 30 30 30 <br /> Height from UDC bottom to highest 11 11 11 <br /> piping penetration <br /> Height from UDC bottom to lowest 3 3 3 <br /> electrical penetration <br /> Condition of UDC prior to testing Dry Dry Dry <br /> Portion of UDC tested Entire Entire Entire <br /> Type of shut-down present Sensor Sensor Sensor <br /> Was sensor removed for testing? Yes Yes Yes <br /> Was sensor properly replaced after testing? Yes Yes Yes <br /> Depth of water level from UDC bottom (in.) 13 13 13 <br /> Wait time for water level to stabilize (hr:min) 0:05 0:05 0:05 <br /> Test start time 12:09 PM 12:09 PM 11:44 AM <br /> Initial Probe Reading 3.9482 5.2947 4.0856 <br /> Test end time 12:24 PM 12:24 PM 11:59 AM <br /> Final Probe Reading 3.9478 5.2952 4.0856 <br /> Test duration (hr:min) 0:15 0:15 0:15 <br /> Change in water level (±0.0000 inches) -0.0004 0.0005 0.0000 <br /> Pass/Fail threshold (±0.0020 inches/}Hr.) 0.0020 0.0020 0.0020 <br /> TEST RESULT PASS PASS PASS <br /> Comments: <br /> © 2010 Walton Engineering,Inc. <br />