MARCH , 1994 <br /> MONTHLY TEST DATA FOR UNDERGROUND PETROLEUM TANKS <br /> GREATER THAN 2000 GALLONS <br /> LLNL—SITE 300 <br /> System ID Test Gain (+) Test <br /> Old New Date Loss (-) Method Comments <br /> Rate (gph) <br /> 865-11D 865-D1U1 1 3/16/94 -0.0108 Horner EZ Check Test showed tank to be leak tight <br /> 871-11D 871-DlU1 3/17/94 1 -0.0105 1 Horner EZ Check Test showed tank to be leak tight <br /> recent test results <br /> 4/25/94 94-081 <br />