Laserfiche WebLink
ANNUAL TEST RESULTS FOR THE PRODUCT AND ♦ APOR OVERFILL CONTAINMENT <br />Name: Lawrence Livermore National Laboratory Date: 10-28-2003 <br />Address: Site 300, Tracy, CA 95376 Bldg: 875 <br />Test Method Developed By: ❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ® Hydrostatic <br />❑ Other (Spec) <br />Equipment Resolution: <br />Test Equipment Used: Caldwell Systems Sump Level Change Indicator 0.0025" <br />Spill Box # <br />Spill Box # <br />Spill Box # <br />Spill Box # <br />875-DlU1 <br />Brian Thornton <br />Nominal Bucket Capacity in 15 gallons <br />gallons: <br />Test fails if the bucket does NA <br />not hold at least 5 gallons <br />Bucket Depth (inside 11.0" <br />measurement): <br />Wait time between filling with 5 minutes <br />water and starting test: <br />Test Start Time: 11:15a <br />Initial Reading (N: 5.25" <br />Test End Time: 11:30a <br />Final Reading (RF): 5.25" <br />Test Duration: 15 minutes <br />Change in Reading (RF -N: 0.00" <br />Pass/Fail Threshold/ Criteria: 0.00" <br />Test Result: ® Pass 0 Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Test water was disposed of in on site in customers oil / water separator. <br />Technician Name: <br />Brian Thornton <br />Signature: <br />