Laserfiche WebLink
'SWRCB,Januar 2002 Page of <br /> c` y <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested <br /> Test Method Developed By: X Spill Bucket Manufacturer Industry Standard Professional Engineer <br /> Other (Specify) <br /> Test Method Used: Pressure Vacuum X Hydrostatic <br /> Other(Specify) <br /> Test Equipment Used: Scale 1/32" Equipment Resolution: 1/32" <br /> ' <br /> Spill Box`# <br /> P Spill Box# Sill Box# <br /> Spill Box# S t <br /> P <br /> Bucket Diameter: 14 inches 14 inches <br /> Bucket Depth: 9 %z" 10 %z" <br /> Wait time between applying <br /> pressure/vacuum/water and 10 Minuites 10 Minutes <br /> starting test: <br /> Test Start Time: 2:30 PM 2:30 PM <br /> Initial Reading(RI): 9 ''/2" 10 %" <br /> Test End Time: 4 PM 4 PM <br /> Final Reading(RF): 9 %i" 10 1/2" <br /> Test Duration: 1.5 Hours 1.5 Hours <br /> Change in Reading(RF-RI): 0 0 <br /> Pass/Fail Threshold or 1/16"Drop 1/16"Drop <br /> Criteria: <br /> Test Result: X Pass ❑Fail X Pass ❑Rail ❑ Pass ❑Fail ❑ Pass ❑Fail <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />