SWRCB,Jany2002 FINALD Page 4 of 7 <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: ❑ Sump Mamifacturer Industry Standard ❑Professional Engineer <br /> ❑other(specify) <br /> Test Method Used: ❑Pressure ❑Vacuum Hydrostatic <br /> ❑Other(S ) <br /> Test Equipment Used: Caldwell Sump Level Change Indicator Equi ent Resolution: 0.0025" <br /> Sump# Sump# Sump# Sump# <br /> 882-D IU2 <br /> Sump Diameter: 36.0" <br /> Sump Depth from Top of Tank: 36.0" <br /> Sump Material: FRP <br /> Height from Tank Top to Top of 17.75" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Top of 15.5" <br /> Lowest Electrical Penetration: <br /> Condition of sump prior to testing: Clean/Dry <br /> Depth of Sump Tested' 19.75" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑Yes[]No UNA ❑Yes❑No[INA ❑Yes[]No❑NA ❑Yes❑No❑NA <br /> roduct and water)?' <br /> Turbine shutdown response time: Suction System <br /> Is system programmed for fail-safe ❑Yes❑No UNA ❑Yes❑No[INA ❑Yes❑No❑NA ❑Yes❑No[INA <br /> shutdown?* <br /> Was fail-safe verified to be ❑yes❑No UNA ❑Yes ONo DNA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> o rational? <br /> Wait time between applying <br /> pressure/vacuum/water and staffing 10 minutes <br /> test: <br /> Test Start Time: 12:25p <br /> Initial Reading(R): 19.75" <br /> Test End Time: 1:10p <br /> Final Reading(RF): 19.75" <br /> Test tion: 45 minutes <br /> Change in Reading(RF-124): 0.00" <br /> Pass/Fail Threshold or Criteria: 0.005" <br /> Test Result ZPass ❑Fail ❑Pass ❑Fail ElPass ❑Fail []Pass ❑Fail <br /> Was sensor removed for testing? OYes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No DNA <br /> Was sensor properly replaced and Yes❑No❑NA ❑Yes❑No[_]NA ❑Yes ONo❑NA ❑Yes❑No❑NA <br /> verified functional after testing? <br /> Comments—(Include information on repairs made prior to testing,and recommended follow-up for failed tests.) <br /> ' ff the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"Nd",then the entire sump should be tested. (See SWRCB LG-160) <br />