Laserfiche WebLink
r r <br /> MW Thornton Environmental t i <br /> y <br /> P.O. Box 360833 Milpitas, CA 95036-0833 <br /> Phone(408)946-1015 ® (209)834-0792 9 Fax(209) 834-0795 <br /> ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR ILL CONTAINMENT <br /> _ Name: Lawrence Livermore National LaboratoryDate: 7-30-2018 <br /> Address: Site 300, Tracy, CA 95376 -� Bldg: 882 <br /> Test Method Developed By: 13 Spill Bucket Manufacturer ®Industry Standard O Professional Engineer <br /> _ ❑Other(Specify) <br /> Test Method Used: ®Hydrostatic— _-_— -- �_-- <br /> ❑Other(Spec) <br /> Test Equipment Used: Caldwell Sump Level Change Indicator — Eq— ment Resolution: 0.0025" — <br /> Spill Box# Spill Box# Spill Box Spill Box# <br /> 882-TFUDOI <br /> Nominal Bucket Capacity in <br /> gallons: <br /> 7.5 Gallons <br /> Test fails if the bucket does Pass <br /> not hold at least 5 allows <br /> --_.__- <br /> Bucket Depth(inside 15" <br /> measurement):_ <br /> Wait time between filling with 5 minutes <br /> water and starting test: <br /> Test Start Time: —4:SOa — -- -------------_. <br /> Initial Reading(R,): 14.75" <br /> Test End Time: 10:12a <br /> kL <br /> Final Reading(RF): 14.75" __---_-----_--------------__ <br /> ENT <br /> Test Duration: 22 minutes — <br /> Change in Reading(RF-Rt): 0.00" -�-- ----- --- <br /> j Pass/Fail Threshold/Criteria: -0.10gph <br /> Test Result ®Pass ❑Fail ❑Pass ❑Fail ' O Pass ❑Fail D Pass 17 Fail <br /> Comments—(include information on re�f)ltl . made prior to lestin , and YecOnnnended fOIPOIV-P��OY fQIICd 1eS15� <br /> Tcst seater was disposed of by LLNL. <br /> TechnicianName:Name: Brian_Thornton Si sture: ._._. . f <br /> -- ---- ----- <br /> ESH-EFA-TKS-18-15666-S M/EM:mw <br />