��unrr: <br />(1W Thornton Environmental Construction, Inc. LILL <br />P.O. Box 360833 Milpitas, CA 95036-0833 <br />Phone (408) 946-1015 9 (209) 834-0792 9 Fax (209) 834-0795 <br />ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br />Name: Lawrence Livermore National Laboratory Date: 7-30-2018 <br />Address: Site 300, Tracy, CA 95376 Bldg: 882 <br />Test Method Developed By: <br />0 Spill Bucket Manufacturer ®Industry Standard 0 Professional Engineer <br />0 Other (Specify) <br />Test Method Used: <br />® Hydrostatic <br />0 Other (Specify) <br />Test Equipment Used: Caldwell <br />Sump Level Change Indicator <br />E ui ment Resolution: 0.0025" <br />Spill Box # Spill Box # Spill Box # <br />Spill Box # <br />882-TFlJDO] <br />Nomina] Bucket Capacity in <br />7.5 Gallons <br />allons: <br />Test fails if the bucket does <br />Pass <br />not hold at least S gallons <br />Bucket Depth (inside <br />15" <br />_ <br />Y <br />measurement): <br />Wait time between filling with <br />5 minutes <br />u <br />water and starling test: <br />i <br />Test Start Time: <br />9:50a <br />Initial Reading (R,): <br />14.75" <br />Test End Time: <br />10:12a <br />Final Reading (Rf)_—_: <br />14.75" <br />Test Duration: <br />1 22 minutes <br />Reading (RF -R;): <br />—._ <br />0.0w, <br />Threshold / Criteria: <br />LTestResult: <br />-0.10gph <br />IM Pass O Fail <br />O Pass 0 Fail <br />O Pass ®Fail <br />❑Pass ❑Fail <br />Comments — ='include lnfonnotion on repairs made prior to testing, and recOPPiPP71P-Pq�for rajled tests) <br />Test water was disposed of by LLNL.� <br />Technician Name: Brian Thornton <br />ESH-EFA-TKS-18-15666-S M/EM: mw <br />