Laserfiche WebLink
j'U L 15 1 91 <br /> GARY FMETERS B4TERPR I SES ENW011k,"i"' <br /> 9449 BUTTERFIELD WY 1A <br /> SACRAMENT09 CA. 95827 <br /> 916-363-9127 <br /> Lic .# 90-1144 <br /> Date : 4-27-91 <br /> Ref . #910427 <br /> To: DAVE CASTRO <br /> U.C.L.L.N.L. <br /> P.O.Box 808 1 -633 <br /> Livermore , Ca. 94550 <br /> Test location : Tank 879-G1U1 , Site 300 . <br /> On 4-27-91 tank testing was completed using the LEAK <br /> COMPUTER tank test system. All testing was done in accordance <br /> with NFPA 329-1983, Section 2643 of the California Underground <br /> Tank Regulations (as revised) and Federal Regulations under 40 <br /> CFR (280-281 ) . The criteria for acceptable tank integrity <br /> allowed by these documents is based upon a detection threshold of <br /> 0 . 10 gallons per hour and a consideration of other specific , <br /> variable factors. Pass/Fail threshold is 0 .05 gal/hr . <br /> LEAK COMPUTER is a certified volumetric tank test system as <br /> specified under federal regulations (40CFR 280) . A copy of this <br /> certification is available on request . The certified protocol <br /> sets out specific operations and procedures. The data below will <br /> satisfy those protocols. <br /> Tank # Comments <br /> G I <br /> product <br /> size a 10 10 0 0 6A7tn <br /> PASS/FAIL i <br /> tank & pipes -AS, <br /> tank only <br /> 2 LEVEL TEST 1 NO 1 Nor <br /> high level <br /> leak rate a 0.07- <br /> X error O.Of <br /> additional data attached <br /> technician signature <br /> 3/91 <br />