Laserfiche WebLink
Ah <br />Ah <br />Continued UNDERGROUND STORAGE TANK (UST) PROGMAM INSPECTION REPORT <br />Facility Address: <br />1403 COUNTRY CLUB BLVD., STOCKTON <br />Inspection Date: <br />5/19/2008 <br />ROUTINE AND MONITORING SYSTEM CERTIFICATION <br />ONSITE TO WITNESS TESTING OF THREE MECHANICAL LINE LEAK DETECTORS. UPON WITNESSING THE TEST ALL THREE <br />PASSED THE THREE GALLON PER HOUR LEAK TEST. <br />ALSO WITNESSED THE ANNUALL MONITORING SYSTEM CERTIFICATION FOR THE WASTE OIL TANK WITH THE RONAN X76 <br />MONITORING PANEL. THE UST HAS TWO SENSORS ONE FOR HIGH LEVEL AND ONE FOR LOW LEVEL FOR THE WET <br />ANNULAR. THE SPILL CONTAINER PASSED THE ONE HOUR HYDROSTATIC TEST. <br />NO ADDITIONAL VIOLATIONS WERE NOTED DURING THIS INSPECTION <br />NOTE: ALL EMD STAFF TIME ASSOCIATED WITH FATLY TO COMPLY BY THE ABOVE NOTED DATES WILL BE BILLED AT THE <br />CURRENT HOURLY RATE ($98.00). <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br />EHD Inspector. <br />Rece' B : <br />Title: <br />Ray von Flue <br />San Joaquin County Environmental Health Department 0 E MaiaR&e6FStoddon CA 95202 • (209) 468-3420 <br />EHD 23-02-002 <br />3/13/2008 <br />Page 2 <br />