Y <br />Garrett Backus [EH] <br />LI <br />From: Garrett Backus [EH] <br />Sent: Wednesday, lune 06, 2012 9:44 AM <br />To: 'r.walton@waltonengineering.com';'m.walton@waltonengineering.com'; Allen Faass <br />Cc: Kasey Foley [EH]; Raymond von Flue [EH]; Willy Ng [EH] <br />Subject: CRLLC 5446 1403 Country Club Blvd waste oil piping sump liquid sensor <br />Attachments: Gravity piping monitoring requirements.pdf, ust_req_table_final_6_08.pdf <br />M <br />I was on site yesterday with Walton Eng. and found that the wiring for the waste oil tank piping sump liquid sensor is <br />disconnected and incomplete. The Ronan monitoring panel may also need a new module to connect the sump sensor. <br />The waste oil tank has double walled gravity flow piping from the oil change bays to the tank. The piping monitoring <br />point is a liquid sensor in the tank top sump. <br />Since double walled gravity flow piping requires continuous monitoring per the attached water board overview <br />document and Title 23, please amend the scope of work for the existing permit to repair the sump liquid sensor wiring <br />and send to me. <br />Here's the water board website link for the attached overview document: <br />http:Hwww.swrcb.ca.gov/water issues/programs/ust/leak prevention/docs/ust req table final 6 08.pdf <br />Thank you, <br />Garrett Backus, Senior Registered Environmental Health Specialist <br />San Joaquin County Environmental Health Department <br />1868 E Hazelton Ave, Stockton, CA 95205-6232 <br />email: gbackus(c)-sjcehd.com <br />telephone: (209) 468-2986 <br />fax: (209) 468-3433 <br />website: http://www.sigov.org/ehd/Programs/UnitlIl/unitiii.htm <br />