Laserfiche WebLink
C <br />SWRCB, January 2002 <br />5. SECONDARY PIPE TESTING <br />0 Pae 2 of 2 <br />Page -- -- <br />Test Method Developed By: <br />❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />® Pressure ❑ Vacuum ❑ Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: 0 —15 PSI GAUGES Equipment Resolution: + / . 0.002" <br />Piping Run # 87 <br />Piping Run # Piping Run # <br />Piping Run # <br />l.P.gMaterial: <br />FIBERGLASS <br />ingManufacturer: <br />AMERON <br />ing Diameter: <br />2"!3" <br />Length of Piping Run: <br />125' <br />Product Stored: <br />87 <br />Method and location of <br />i in -run isolation: <br />TEST BOOT !STP <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 MIN <br />Test Start Time: <br />10:30 AM <br />Initial Reading (RI): <br />5.0 PSI <br />Test End Time: <br />11:30 AM <br />Final Reading (RF): <br />5.0 PSI <br />Test Duration: <br />1 HR <br />Change in Reading (RF -RI): <br />0 PSI <br />Pass/Fail Threshold or <br />Criteria <br />NO LOSS <br />NO LOSS NO LOSS <br />NO LOSS <br />� � Piss ❑,)(�ni1" j� '��s ❑ �'ttil ❑pass ❑Fail ❑ P��s �.��,. <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />RETEST - 6 MONTH FOLLOW UP AFTER REPAIRS MADE BY ANOTHER CONTACTOR <br />