Laserfiche WebLink
SWRCB, January 2002 <br />0 <br />a CPTT.T./nVF.RFTT.T. rnNTATNMF,NT BOXES <br />0 C T 19 9WS_7_ of _8 - <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />ENVIRONMENTAL HEALTH <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />DEPARTMENT <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer <br />❑ Other (Spec) <br />® Industry Standard <br />❑ Professional Engineer <br />Test Method Used: <br />❑ Pressure <br />❑ Other (Specify) <br />❑ Vacuum <br />® Hydrostatic <br />Test Equipment Used: VISUAL <br />— TAPE MEASURE <br />Spill Box # DIESEL <br />FILL <br />Equipment Resolution: 1/16" <br />Spill Box # DIESEL Sill Box # 87 FILL <br />VAPOR p <br />Spill Box # 87 <br />VAPOR <br />Bucket Diameter: <br />12" <br />12" <br />12" <br />12" <br />Bucket Depth: <br />12.25" <br />11.75" <br />12.25" <br />11.25" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 MIN <br />10 MIN <br />10 MIN <br />10 MIN <br />Test Start Time: <br />8:15 <br />8:15 <br />8:15 <br />8:15 <br />Initial Reading (R,): <br />10.75" <br />9.75" <br />10.75" <br />9.75" <br />Test End Time: <br />9:15 <br />9:15 <br />9:15 <br />9:15 <br />Final Reading (RF): <br />10.75" <br />9.75" <br />10.75" <br />9.75" <br />Test Duration: <br />1 HR <br />1 HR <br />1 HR <br />1 HR <br />Change in Reading (RF -R,): <br />0 <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or <br />Criteria: <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />Test Result: <br />® Pass ❑ Fail <br />® Pass <br />❑ Fail I ® Pass <br />❑ Fail <br />® Pass ❑ Fail <br />Comments —(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />