Laserfiche WebLink
SECONDARY LINE TESTING DEC 17 2013 <br />ENVIRONMENTAL <br />HEALTH DEPARTMENT <br />Test Method By: o Manufacturer • Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: • Pressure o vacuum o Hydrostatic o Other (see below) <br />Measuring Equipment Used: Pressure Gauge (range 0 to 15 psig) <br />Descrintion Line *1 Line *2 Lino #3 <br />Tank product <br />Pipe manufacturer <br />Diesel <br />Ameron <br />Gasoline - 87 <br />Ameron <br />Gasoline - 91 <br />Ameron <br />Pipe material <br />FRP <br />FRP <br />FRP <br />Primary pipe diameter (inches) <br />2 <br />2 <br />2 <br />Secondary pipe diameter (inches) <br />3 <br />3 <br />_ <br />3 <br />Method of secondary pipe isolation <br />Termination Boot <br />Termination Boot <br />Termination Boot <br />Location of secondary pipe isolation <br />Sump <br />Sump <br />Sump <br />Estimated length of piping run (feet) <br />120 <br />120 <br />120 <br />(include length of branch runs) <br />_ <br />Wait time for pressure to stabilize (hr:min) <br />0:05 <br />Test start time <br />10:20 AM <br />Initial pressure (psig) <br />5.0 <br />Test end time <br />Final pressure (psig) <br />11:20 AM <br />5.0 <br />Test duration (hrmin) <br />1:00 <br />Change in pressure (psig) <br />0.0 <br />Pass/Fail threshold (psig) <br />0.5 <br />TEST RESULT <br />PASS <br />Comments: <br />This is a retest of the 87 secondary line only. <br />© 2013 Walton Engineering, Inc. <br />