Laserfiche WebLink
PRESSURIZED PIPING LEAK DETECTION CERTIFICATION SHEET <br />Date: 512012013 <br />Location: CRLLC #5446 <br />1403 COUNTRY CLUB BLVD <br />STOCKTON CA 95204 <br />Work Order # 13052001-7 <br />Contact: ALLEN FAASS <br />Telephone: (925) 884-0800 <br />SUMP # <br />3/4 <br />3/4 <br />3/4 <br />PRODUCT <br />DIESEL <br />87 <br />91 <br />LD TYPE Mechanical, (W)PLLD, (P)LLD I <br />M <br />M <br />M <br />LD MANUFACTURER <br />VMI <br />VMI <br />VMI <br />LD MODEL <br />LD2000 <br />LD2000 <br />LD2000 <br />LD SERIAL NUMBER <br />01081406 <br />11071267 <br />08061020 <br />SUMP CONDITION <br />DRY <br />DRY <br />DRY <br />RESILIENCY <br />150 ML <br />200 ML <br />185 ML <br />OPERATING PRESSURE <br />28 PSI <br />28 PSI <br />28 PSI <br />OPENING TIME <br />3 SEC <br />3 SEC <br />3 SEC <br />METERING PRESSURE <br />10 PSI <br />10 PSI <br />10 PSI <br />FUNCTIONAL ELEMENT HOLDING PRESSURE <br />22 PSI <br />22 PSI <br />18 PSI <br />LEAK RATE LD DETECTED <br />3 GPH <br />3 GPH <br />3 GPH <br />DOES LD DETECT 3 GPH LEAK RATE? <br />YES <br />YES <br />YES <br />DOES VEEDER-ROOT CONSOLE ALARM? <br />N/A <br />N/A <br />N/A <br />LD PASS OR FAIL? <br />PASS <br />PASS <br />PASS <br />Comments: <br />Technician: RICHARD THOMAS <br />Signature: <br />Contractor Lic. # 803705 <br />TANK"TEK ENVIRONMENTAL CORPORATION <br />607 Elmira Road, PMB 336, Vacaville, CA 95687 — Ph. (707) 446-6151 - Fax (707) 446-6192 <br />31828 Cercle Chambertin, Temecula, CA 92591 — Ph. (951) 699-8058 - Fax (951) 699-8059 - E-mail: bballreich@verizon.net <br />