Laserfiche WebLink
t <br /> e_ <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> F <br /> N E: HAMMER/ 1-5 ARCO 3250 Hammer DATE; 06/15/2006 WORK ORDER 2243262 <br /> ADDRESS: 3250 W HAMMER LANE STOCKTON CA 95209 <br /> SON FOR TEST: lGroundwater Level("from grade): <br /> TANK INF RMATION AND INTERSTITIAL TEST <br /> Product Tank Size Dia' Depth Start initial Fnish Final Pass/ <br /> an <br /> Material Manufacturer Test Method Time Level Time Result Fail <br /> 1 REGULAR 12000 92 DW FIBERG Owens Coming Vacuum 8:06 10" -Hg 9:08 10" eHg PASS <br /> 2 REGULAR 12000 92 DW FIBERG Owens Coming Vacuum 8:10 10' "Hg 9:10 1T "Hg PASS <br /> 3 SUPREME 12000 92 DW FIBERG Owens Coming Pressure 8:20 10' psi 9:20 10" psi PASS <br /> 4 <br /> 5 <br /> 6 <br /> 7 <br /> 8 <br /> Comments: <br /> LINE INFORMATION AND INTERSTITIAL TESTS <br /> Dia. Len, Volume Start Initial Finish Final Pass/ <br /> Tan Product feet` Material Manufacturer (gaVons Test Method Time Level Time Result Fail <br /> 1 reg slave fiberglass Smith Pressure 7:37 3psi psi 8:37 3psi psi PASS <br /> 2 reg fiberglass Smith Pressure 7:40 3psi psi 8:40 3psi psi PASS <br /> 3 sup fiberglass Smith Pressure 7:45 3psi p� 8:45 3psi Psi PASS <br /> 4 m9 2 fiberglass Smith Pressure 7:55 3psi psi 8:55 3psi psi PASS <br /> 5 sup 2 fiberglass Smith Pressure 8:40 3psi psi 9.40 3psi psi PASS <br /> 6 <br /> 7 <br /> 8 <br /> Comments: <br />