• <br />UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />Test Method Developed By: ❑ UDC Manufacturer ❑ Industry Standard ❑ Professional Engineer <br />® Other (Specify) Caldwell Sump Tester <br />Test Method Used: ❑ Pressure ❑ vacuum ® Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Caldwell Sump Tester <br />Equipment Resolution: 0.005 inches in <br />UDC#1 <br />UDC #2 <br />UDC #3 <br />UDC# <br />UDC Manufacturer: <br />Bravo <br />Bravo <br />Bravo <br />Bravo <br />UDC Material: <br />Plastic <br />Plastic <br />Plastic <br />Plastic <br />UDC Depth: <br />8 inches <br />8 inches <br />8 inches <br />8 inches <br />Height from UDC Bottom to <br />0 inches <br />0 inches <br />0 inches <br />0 inches <br />Top of Highest Piping <br />Penetration: <br />Height from UDC Bottom to <br />N/A <br />N/A <br />N/A <br />N/A <br />Lowest Electrical Penetration: <br />Condition of UDC prior to <br />Dry <br />Dry <br />Dry <br />Dry <br />testing: <br />Portion of UDC Tested <br />6 inches <br />6 inches <br />6 inches <br />6 inches <br />Does turbine shut down when <br />®Yes ❑No ❑N/A <br />®Yes ❑No [—]N/A <br />®Yes ❑No ❑N/A <br />®Yes ❑No ❑N/A <br />UDC sensor detects liquid <br />Turbine shutdown response <br />3 sec <br />3 sec <br />3 sec <br />3 sec <br />time <br />Is system programmed for <br />®Yes ❑No ❑N/A <br />®Yes ]No ❑N/A <br />®Yes ❑No ❑N/A <br />®Yes ❑No ❑N/A <br />fail-safe shutdown <br />Was fail-safe verified to be <br />®Yes ❑No ❑N/A <br />®Yes [:]No[—]N/A <br />®Yes ❑No [:]N/A <br />®Yes ❑No ❑N/A <br />operational <br />Wait time between applying <br />pressure/vacuum/water and <br />5 minutes <br />5 minutes <br />5 minutes <br />5 minutes <br />starting test <br />Test Start Time: <br />10:30 <br />11:15 <br />12:00 <br />12:45 <br />Initial Reading (R,): <br />2"d Rin <br />2"d Ring <br />2nd Ring <br />2nd ring <br />Test End Time: <br />11:-00 <br />11:45 <br />12:30 <br />13:15 <br />Final Reading (RF): <br />2nd Ring <br />2nd Ring <br />2nd Ring <br />2nd ring <br />Test Duration: <br />30 minutes <br />30 minutes <br />30 minutes <br />30 minutes <br />Change in Reading (RF -R,): <br />0 Change <br />0 Change <br />0 Change <br />0 Change <br />Pass/Fail Threshold or Criteria: <br />0.005 inches in 1/2 <br />0.005 inches in <br />0.005 inches in 1/2 <br />0.005 inches in 1/2 <br />hour <br />1/2 hour <br />hour <br />hour <br />Test Result: <br />® Pass , ❑ Fail <br />®; Pass El <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />Fail <br />Was sensor removed for <br />®Yes ❑No ❑N/A <br />®Yes ❑No ❑N/A <br />®Yes ❑No ❑N/A <br />®Yes ❑No ❑N/A <br />testing? <br />Was sensor properly replaced <br />and verified functional after <br />®Yes ❑No ❑N/A <br />®Yes [—]No ❑N/A <br />®Yes [:]No [—]N/A <br />®Yes ❑No ❑N/A <br />testing? <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed <br />tests) <br />