SWRCB,January 2002 Page of <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: ❑Sump Manufacturer ❑Industry Standard X Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution:.002 <br /> Sump#1 Sump#2 Sump# Sump# <br /> Sump Diameter: 36" 36" <br /> Sump Depth: 24" 24" <br /> Sump Material: Fiberglass Fiberglass <br /> Height from Tank Top to Top of 11" 10" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 19" 18" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry Dry <br /> Portion of Sump Tested' Water Level 21" Water Level 20" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both No No <br /> product and water)?* <br /> Turbine shutdown response time N/A N/A <br /> Is system programmed for fail-safe Yes Yes <br /> shutdown?' <br /> Was fail-safe verified to be No No <br /> operational?* <br /> Wait time between applying water 5 Minutes 5 Minutes <br /> and starting test: <br /> Test Start Time: 10:10 10:15 <br /> Initial Reading(RI): .001 .001 <br /> Test End Time: 10:40 10:45 <br /> Final Reading(RF): .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes <br /> Change in Reading(RF-RI): 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes <br /> Test Result: X Pass ❑Fail X Pass 0 Fail 0 Pass ❑Fail 0 Pass ❑Fall <br /> Was sensor removed for testing? X Yes ❑No ❑NA X Yes ❑No ❑NA ❑Yes ❑No [INA ❑Yes ❑No ❑NA <br /> Was sensor properly replacedand <br /> verified functional after testin ? X Yes ❑No ElNA X Yes ❑No [INA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Suction System. <br /> ' If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />