Laserfiche WebLink
OIL EQUIPMENT SERVICE <br />Division of Keith A. Tallia, lac. <br />STATE. 1.lCFNSE: No. 323417 <br />It.ASSIFICATION: A-ILA"L., ('61I)40 <br />STATE: ENVIRONMENTAL ASSESSOR Nu. 111781 <br />Telephone: (209) 754-1808 <br />Fax: (209) 754-5726 <br />LEAK DETECTOR TEST RECORD Post Office Box 950 <br />750 Industrial Way <br />SAN ANDREAS. CALIFORNIA 95249 <br />• Customer Date <br />Norms 76 11/4/02 <br />Location <br />633 E. Victor Rd., Lodi, CA <br />Technician <br />James P. Hesketh <br />Manufacturer <br />Tokheim <br />Manufacturer <br />Red Jcket FX1 V <br />Product <br />Mid Grade____ <br />Submersible Pump Identification <br />Model No. Serial Number <br />585-34 585-22864 <br />Leak Detector Identification <br />Description Other Stvle Leak Dc!c('o1 <br />Diaphragm-type— <br />Piston-type--X— <br />Tamper-proof <br />iaphragm-typePiston-typeX <br />Tamper-proof seal installed? Yes No X <br />Leak Detector in Submersible Pump <br />Test at Dispenser <br />I. Operating Pump Pressure psi (para. 15) <br />2. Gallons per hour rate 3 (para. 22) <br />3. Line pressure with pump shut off 26 psi (para. 23) <br />4. Bleedback Test with pump off 120 mi (para. 26) <br />5. Step -through time to full flow 3 seconds (para. 30) <br />r <br />6. Leak detector stays in leak search position. (para. 42) Yes_X — <br />LEAK DETECTOR TEST <br />Note: Pass = t.cak detector fits test protocol <br />Fall =teak detector fails test protocol <br />Pass_ X -- <br />Fail. -- <br />- <br />Hail.-- _. -- ------ <br />No <br />*Complete thermal expansion test <br />before failing leak detector. <br />-- - .02 <br />c K nX'T Dale <br />James P. Hesketh <br />