• ,Sura -O6 -d2 12:29P Beau u Electric Inc. 860 4 uaes�� r -u1 <br />s <br />MEMORANDUM <br />TO: <br />bEs <br />BZ MAENT.ENANCE <br />FROM: <br />JIM G0ODMAN <br />SUBJECT: BEAUDREAC; INTFRV ACE TO TLS -350 <br />DATE: <br />JUNE 6, 2002 <br />CC: <br />SACRAIvit✓NTO COUNTY REGULATORS <br />The interfaei: between die 522 Remote Monitoring System and the TLS -350 works as follows, the <br />522 demote Monitoring Systcttt has a single N/C relay output (see drawing below) for <br />cvrnmunieating fuel alarm suitus. When a fuel alarm occurs. the N/C relay opens. The Veedcr <br />Root TLS -350 allows for third -party external inputs through an 1;VMt/(hitput Combination <br />,Module (Veeder Root Part 11323400-00x). The 1/0 Module has two 24 volt alarm loops diet can <br />be controlled by a mmotc N/C relay. The drawing shown. below shows the connections trade at <br />the 522 Rernote Monitor for outputting fuel alarm status to the 1/0 Module, Using; 19 g;augc or <br />smaller conductors, tine installer must aomect 2 eottductors to the 522 remote Monitoring <br />System (as show -n below). This cable is then connected to the TLS -350 per Veeder-Root <br />instruction; for the Veeder-Root 1/0 Module (VrR Manual No. 576013-614) and the TLS -350 is <br />then programmed as required for turbine shutdown. WC tecomtnend that the TLS -350 input be <br />identified as `°Seaudreaa SyStcrn". <br />c,w=t ri "Wo W1* 4 + saw* <br />000duuton to 1 oat <br />co IMaduln (WW VMW*f K"t <br />Pan 63 <br />20'd 808Stib2 9SS SWJJd d31UM Nd8-13/93 MS b2:9Z E00E-9Z-100 <br />