Laserfiche WebLink
OIL EQUIPMENT SERVICE <br />Division of Keith A. 7allia, lrte. <br />LEAK DETECTOR TEST RECORD <br />Customer <br />Norms 7E <br />n <br />STATE LICF.NSF: No. 323417 <br />CLASSIFICATION: A-IIA"L., C611)40 <br />STATE. ENVIRON11IEN'I'AL %SSI-:SSOR No. 01781 <br />Telephone: (209) 754-1808 <br />Fax: (209) 754-5726 <br />Post Office Box 950 <br />750 Industrial Way <br />SAN ANDREAS. CALIFORNIA 95249 <br />Date <br />7/19/02 <br />633 E. Victor Rd., Lodi, CA 95240 <br />Technician Product <br />James P. Hesketh lRegular <br />Submersible Pump Identification <br />Manufacturer Model No. Serial Number <br />Tokheim 100505-34 <br />` Leak Detector Identification <br />Manufacturer Description Other StvIc I.Cak_1)ctccto r <br />Red Jacket FX1 V Diaphragm-type— <br />Piston-type-_X_ <br />iaphragm-typePiston-typeX <br />Tamper -proof seal installed? Yes No X <br />Leak Detector in Submersible Pump <br />Test at Dispenser <br />I. Operating Pump Pressure---3-0_psi (para. 15) <br />2. Gallons per hour rate 3 (para. 22) <br />3. Line pressure with pump shut off __3_0 psi (para. 23) <br />4. Bleedback Test with pump off 1 40 ml (para. 26) <br />5. Step -through time to full flow 3 seconds (para. 30) <br />6. Leak detector stays in leak search position. (para. 42) Yes—X_ <br />No <br />LEAK DETECTOR TEST *Complete thermal expansion test <br />Note: Pass = Leak detector tits test protocol before failing leak detector. <br />Fall = Leak detector fails test protocol <br />Pass___ <br />Fail _- ----- <br />- <br />T "chn 0611ar Dat - e <br />times P. Hesketh <br />