Laserfiche WebLink
OIL EQUIPMENT SERVICE <br />Division of Keitit A. Tallia, Inc. <br />LEAK DETECTOR TEST RECORD <br />Customer <br />Norm's 76 <br />STATE LICENSF: No. 323417 <br />CLASSIFICATION: A-ILl7.., C611D40 <br />STATF; ENVIRONMENTAL ASSESSOR No. 01781 <br />Telephone: (209) 754-1808 <br />Fax: (209) 754-5726 <br />Post Office Box 950 <br />750 Industrial Way <br />SAN ANDREAS, CALIFORNIA 95249 <br />Date <br />6/7/02 <br />633 E. Victor Rd., Lodi, CA 95240 <br />Technician Product <br />Bruce K. Kieffaber _ Regular <br />Submersible Pump Identification <br />Manufacturer Model No. Serial Number <br />Tokheim 100585-34 58522865 <br />Leak Detector Identification <br />Manufacturer Description Other Style Leak l )ciectm <br />Red Jacket Diaphragm -type X <br />Piston -type <br />Tamper -proof seal installed? Yes No X <br />Leak Detector in Submersible Pump <br />Test at Dispenser <br />1. Operating Pump Pressure 2 8 psi (para. 15) <br />2. Gallons per hour rate 3 (para. 22) <br />3. Line pressure with pump shut off 28 psi (para. 23) <br />4. Bleedback Test with pump off 200 ml (para. 26) <br />5. Step -through time to full flow 2 _seconds (para. 30) <br />6. Leak detector stays in leak search position. (para. 42) Yes X _ <br />No <br />LEAK DETECTOR TEST *Complete thermal expansion test <br />Note: Pass Leak detector fits test protocol before failing leak detector. <br />Fail = Leak detector tails test protocol <br />Pass_ X __ <br />Fail — - ____ _ <br />�, 6/7/02 <br />6c nician Date <br />Bruce K. Kieffaber <br />