Laserfiche WebLink
OIL EQUIPMENT SERVICE <br />Division of Keith A. Talliu, Inc. <br />LEAK DETECTOR TEST RECORD <br />Customer <br />Norms 7b <br />Location <br />633 E. Victor Rd., Lodi, CA 95240 <br />Technician <br />James P. _Hes <br />Manufacturer <br />Tokheim <br />Manufacturer <br />Red Jacket <br />116-056 <br />11 <br />STATE LICENSE: No. 323417 <br />CLASSIFICATION: A -11A7.., C6111)40 <br />STATE; ENVIRtâ–ºNMF.NTA1, ASSESSOR No. 01781 <br />Telephone: (209) 754-1808 <br />Fax: (209) 754-5726 <br />Post Office Box 950 <br />750 Industrial Way <br />SAN ANDREAS, CALIFORNIA 95249 <br />_Date <br />---- --6/8/01. _ <br />Product <br />-I Super <br />Submersible Pump Identification <br />Model No. Serial Number <br />585-34 585 22865 <br />Leak Detector Identification <br />Description Uthcr Stvlc_Lcak th!eclm <br />Diaphragm -type <br />Piston -type X <br />Tamper -proof seat installed? Yes No <br />Leak Detector in Submersible Pump <br />Test at Dispenser - <br />1. Operating Pump Pressure 2 8 psi (para. 15) <br />2. Gallons per hour rate 3 (para. 22) <br />3. Line pressure with pump shut off 24 psi (para. 23) <br />4. Bleedback Test with pump off 120 ml (para. 26) <br />5. Step -through time to full flow 3__seconds (para. 30) <br />6. Leak detector stays in leak search position. (para. 42) Yes X <br />No <br />LEAK DETECTOR TEST <br />Note: Puss = t.eak detector fits test protocol <br />Fail = teak detector fails test protocol <br />Fail <br />*Complete thermal expansion test <br />before failing leak detector. <br />6/8/01 <br />Technician I)aI-e <br />James P. Hesketh <br />