Laserfiche WebLink
I We <br />XTI <br />Integrity Tank Testing Systems, Inc. <br />June 13, 1991 <br />Mr. Keith Tallia <br />OIL EQUIPMENT SERVICE <br />P. O. Box 950 <br />San Andreas, California 95249 <br />Site: KNOX'S BP FOOD MART <br />633 East Victor Road <br />Lodi, California <br />Dear Mr. Tallia: <br />Following is a summary of the precision testing we recently <br />conducted on your underground storage tank. <br />Enclosed are copies of the test worksheets, graphs, and/or <br />computer summation for your submittal to the appropriate <br />governmental agency. Individual computer generated readings <br />will be forwarded as requested. <br />A tank system may be considered tight, according to the <br />current regulations if the the test results shown below do <br />not exceed 0.05 gph. If the results are beyond this <br />parameter, an unauthorized release may have occurred, and <br />you should consider taking remedial action. <br />TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br />LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br />East 12,000 <br />Middle 12,000 <br />West 12,000 <br />Please contact us <br />information. <br />Sincer ly, <br />le <br />W. N. Savage <br />Certified Tester <br />Prem U/L -.001 Yes <br />Reg Gas +.004 Yes <br />U/L Gas +.009 Yes <br />if you need additional assistance or <br />800 262-8378 166 FYaak West Circle Stockton, CA 95206 (209) 466-8036 <br />