Laserfiche WebLink
HAZARDOUS MATERIAL MANAGEMENT PLAN & UST MONITORING PLAN <br />DEALER: A.P.S.I. OWNER: CHEVRON, U.S.A. <br />BUSINESS NAME: APSI Chevron P.O.BOX 5004 <br />STREET: 1960 WEST 11TH STREET SAN RAMON, CA 94583-0804 <br />CITY• Tracy CA ZIP: 95376 <br />STATION No: 201383 <br />SITE PHONE 209-836-3181 <br />DUNN & BRADSTREET J 00-914-0559 SIC CODE: 5541 5411 7542 <br />NATURE OF BUSINESS: <br />GASOLINE SALES X AUTO REPAIR CAR WASH X FOOD MARTX <br />EXISTING UNDERGROUND TANKS ARE AS FOLLOWS: <br />No. of <br />SIZE <br />MATERIAL <br />CONST . <br />SPILL <br />OVERFILL <br />TANKS <br />(gal) <br />(STL/FG) <br />(SW/DW) <br />(YIN) <br />(YIN) <br />SUPER UNLEADED 1 <br />12000 <br />FG <br />DW <br />Y <br />y <br />REGULAR UNLEADED 1 <br />12000 <br />FG <br />DW <br />y <br />Y <br />PLUS UNLEADED 1 <br />12000 <br />FG <br />DW <br />Y <br />y <br />DIESEL <br />WASTE OIL <br />PRODUCT LINES: MATERIAL: FG <br />CONSTRUCTION: Double Wall <br />LINE LEAK DETECTION METHOD: X ELECTRONIC MECHANICAL <br />All product lines have line leak detectors capable of detecting a leak <br />of 3 gallons or more per hour at 10 lbs. per square inch line pressure <br />within 1 hour; see page one for a description of the equipment <br />installed at this location. <br />All product lines are pressurized using a submerged pumping system and <br />are tested annually to assure the leak detectors are functional.Impact <br />valves are also inspected annually to assure closure. <br />Repair and/or replacement of all leak detectors and impact valves will <br />be done annually at the time of inspection and retested to meet the <br />above test conditions. <br />* This document is to be kept current and at the site. Revision 8,-1991 <br />1 <br />