Laserfiche WebLink
TLS -350 1360 PC I 35OR I 35f)RPC <br />Solid -State Pan/Sump Sensor (794380-321, -351), Piping Sump Swum (794380-2081 <br />Micro Sensor (794380-340) <br />Output type: qualitative <br />Sampling frequency'. cortinuous <br />Operating principle: product permeablefultrasonicifloat switch <br />Test Resuft <br />unleaded <br />gglioline <br />diesel fuel <br />water <br />P�tp'�S umea ens�q7 94�380-20�8 <br />Min. Product level (cm) <br />3.51 <br />3.40 <br />3,03 <br />Precision <br />0.011 <br />0,011 <br />0.011 <br />Detection time (sec) <br /><1 <br /><1 <br /><1 <br />fioil d&�tsPa�nf �Sn or �7943�80-321�-351 <br />Min. product thickness (cm) <br />2.60 <br />2.50 <br />260 <br />Precision <br />0.010 <br />0.010 <br />0.010 <br />Detection time (sec) <br /><1 <br /><1 <br /><1 <br />Kicro en or a9438Q:��40 <br />Min, product thickness (cm) <br />0.51 <br />0.46 <br />0.48 <br />Precision <br />0 11 <br />0.007 <br />0-007 <br />Detection time (sec) <br /><1 <br /><1 <br /><1 <br />Comments: <br />Test procedures used were modified by evaluator from EPNs "Standard <br />Test Procedures for Evaluation Leak Detection Methods; Lquid-Phase Out -of -Tank Product <br />Detectors," March 1990. <br />Detector is reusable. <br />Veeder-Roct Evaluator: Ken Wilcox Associates. <br />125 Powder Forest Dr. Tel: (816) 443-2494 <br />Simsbury, CT 06070-2003 <br />Tel: (203) 651-2700 Date of Evaluation., I CV20194 <br />equipment Equipment should be Installed and operated h accordance vAh all applicable lam and requWom. <br />